SUNNY TRIPOWER  Inverters


Sunny Tripower 10000TL / 12000TL / 15000TL / 17000TL

The Tripower is in a class of its own. This inverter is packed with state-of-the-art technology and is designed for easy installation, high yield, and secure grid support. Thanks to its multi-string technology and the widest input voltage range, the three-phase inverter is suitable for every imaginable module configuration. In addition, it is highly flexible in terms of the plant design - from 10 kW up to the megawatt range.

The Sunny Tripower presently fulfills the BDEW guideline requirements (medium voltage guideline), and in so doing, it participates in reliable grid management. A comprehensive security concept encompassing, among other things, string failure detection, electronic string fuses, and an integrable surge protection device type II, providing the highest level of availability and reducing plant costs.

  • Maximum efficiency of 98 %
  • Highest yields through OptiTrac and OptiCool
  • Compatible with the BDEW guidelines
  • Integrated ESS DC load disconnecting unit
  • Electronic String Fuse and String Failure Detection
  • String Current Monitoring
  • DC Surge Protection Device (type II) can be integrated
  • DC input voltage of up to 1000 V
  • Flexible system design using two separate step-up converters
  • Three-phase feed-in
  • Cable connection without tools
  • Innovative DC plug system
  • Convenient wiring compartment
  • Bluetooth Communication

Input (DC)Sunny Tripower
10000TL
Sunny Tripower
12000TL
Sunny Tripower
15000TL
Sunny Tripower
17000TL
Max. DC power (at cos φ = 1)10.4 kW12.5 kW15.6 kW17.6 kW
Max. DC voltage1000 V1000 V1000 V1000 V
PV-voltage range, MPPT150 – 800 V150 – 800 V150 – 800 V150 – 800 V
Max. input current (input A / input B)22 A / 11 A22 A / 11 A33 A / 11 A33 A / 11 A
Number of MPP trackers2222
Max. number of parallel strings (input A / input B)4 / 14 / 15 / 15 / 1

Output (AC)    
Nominal AC ouput10 kVA12 kVA15 kVA17 kVA
Max. AC power10 kVA12 kVA15 kVA17 kVA
Max. output current16 A19.2 A24 A24.6 A
Nominal AC voltage3 / N / PE,
230 / 400 V
3 / N / PE,
230 / 400 V
3 / N / PE,
230 / 400 V
3 / N / PE,
230 / 400 V
AC grid frequency (self-adjusting) / range50 Hz / 60 Hz /
± 4.5 Hz
50 Hz / 60 Hz /
± 4.5 Hz
50 Hz / 60 Hz /
± 4.5 Hz
50 Hz / 60 Hz /
± 4.5 Hz
Phase shift (cos φ), adjustable0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
0.8 leading ...
0.8 lagging
AC connectionThree-phase Three-phase Three-phase Three-phase

Data Sheet

 


                                                                                                                                Back to top