SMA Windy Boy Inverters


The grid-coupling of small wind energy plants is simpler than ever with the Windy Boy from SMA. It converts the variable frequency voltage from wind generators into grid conforming AC voltage. Thus the energy can be used privately, excess energy fed into the mains grid and respectively remunerated. The Windy Boy works perfectly together with the Sunny Island in stand-alone grids for the electrification of remote areas.

The Windy Boys are suitable for wind generators from a wide variety of manufacturers and power classes. They guarantee an optimal power adjustment and very high energy yields.

They are also best suited for flexible and worldwide use - ensured by the robust housing, the SMA Grid Guard disconnection device, the electric separation to the grid along with an automatic 50 or 60 Hz recognition.   

                                                                                                                                                                                             

Windy Boy 1100LV  

The Windy Boy 1100LV is the perfect solution for small wind power plants with low generator voltage: Turbines with 24 or 48 V nominal voltage can be connected without an additional voltage transformer. The programmable MPP characteristic curve offers the greatest possible freedom for choosing the turbine, while the weather-proof casing and the wide temperature range allow for installation at almost any location. As an inverter for wind power plants, the Windy Boy is optimally adjusted to the frequent load changes. Its minimal internal consumption during still air increases yield even more, which can be monitored at any time on the display or any of several communication interfaces   

  • Specially designed for small wind energy plants
  • Excellent performance with weak wind
  • Free choice of turbines thanks to programmable characteristic curve
  • Free choice of installation site
  • Galvanic isolation
  • In accordance with almost all European grid connection guidelines
  • Worldwide SMA Service including Serviceline
  • Comprehensive SMA warranty program

Input (DC)WB1100LV
Max. DC power1210 W
Recommended generator power at 2500 full-load hours per year1000 W
Recommended generator power at 5000 full-load hours per year900 W
Max. DC voltage60 V
Min. open circuit voltage for activating "turbine mode"25 V
Operating range "turbine mode"21 V – 60 V
Max. input current62 A

Output (AC) 
Nominal AC power1000 W
Max. AC power1100 W
Max. output current5 A
Nominal AC voltage / AC operating range220 V – 240 V / 180 V – 260 V
AC grid frequency (self-adjusting) / range50 Hz / 60 Hz / ± 4.5 Hz
Phase shift (cos φ)1
AC connectionsingle-phase

Data Sheet

                                                                                                                                                                                              Back to top

 Windy Boy 1100 / 1200 / 1700

The Windy Boys 1100, 1200 and 1700 are perfectly suitable for small wind energy plants. The programmable power curve enables optimal adaptation to the characteristics of the wind turbine and therefore increases the yield. Its weatherproof housing and the wide temperature range allow the installation in almost every location. The devices are optimally adjusted to fast and frequent load changes and, with the optimal Windy Boy Protection Box, provide the perfect interface for any turbine. Using the integrated display and different communication interfaces you can monitor all plant values at any time. And should there still be any problems: The worldwide SMA service and the comprehensive warranty program ensure maximum security.

  • Specially designed for small wind energy plants
  • Freely configurable power curve
  • Free choice of mounting location
  • Certified for the most important countries of installation (SMA grid guard)
  • Electric separation
  • Compatible with Windy Boy Protection Box 400
  • Worldwide SMA service and SMA Service Line
  • Comprehensive SMA warranty program

Input (DC)WB1100WB1200WB1700
Max. DC power1210 W1320 W1850 W
Recommended generator power at 2500 full-load hours per year1000 W1050 W 
Recommended generator power at 5000 full-load hours per year900 W1000 W1300 W
Max. DC voltage400 V400 V400 V
Min. open circuit voltage for activating "turbine mode"150 V120 V150 V
Operating range "turbine mode"139 V – 400 V100 V - 400 V139 V – 400 V
Max. input current10 A12,6 A12.6 A

Output (AC)   
Nominal AC power1000 W1200 W1550 W
Max. AC power1100 W1200 W1700 W
Max. output current5.6 A6,1 A8.6 A
Nominal AC voltage / AC operating range220 V – 240 V / 180 V – 260 V220 V – 240 V / 180 V – 260 V220 V – 240 V / 180 V – 260 V
AC grid frequency (self-adjusting) / range50 Hz / 60 Hz / ± 4.5 Hz50 Hz / 60 Hz / ± 4.5 Hz50 Hz / 60 Hz / ± 4.5 Hz
Phase shift (cos φ)111
AC connectionsingle-phasesingle-phasesingle-phase

Data Sheet


                                                                                                                                                                                              Back to top

Wind Boy 2500 / 3000  

The Windy Boy 2500 and 3000 are ideal for small wind energy plants: with more than 10,000 units, they are successfully in use worldwide. They feature a maximum efficiency of 95 %. The programmable MPP characteristic curve enables an optimal adjustment to the characteristic curve of the turbine, which is also protected by a special smooth start device. The worldwide serviceable SMA Grid Guard interface is also used with this Windy Boy. It ensures maximum reliability for the operation of the wind energy plant and allows for the feeding-in to almost any public grid.

  • Control optimized for wind energy plants
  • Up to 95 % efficiency
  • Protection of the turbine through smooth start
  • Freely configurable MPP characteristic curve
  • Free choice of installation site
  • Certified for the most important countries of Installation (SMA Grid Guard)
  • Galvanic isolation
  • Compatible with the Windy Boy Protection Box 600
  • Proven technology, 10,000 times tried and tested
  • Worldwide SMA Service including Serviceline
  • Comprehensive SMA warranty program

Input (DC)WB2500WB3000
Max. DC power2700 W3200 W
Recommended generator power at 2500 full hours per year2100 W2500 W
Recommended generator power at 5000 full hours per year1900 W2200 W
Max. DC voltage600 V600 V
Min. open circuit voltage for activating "turbine mode"250 V290 V
Operating range "turbine mode"224 V – 600 V268 V – 600 V
Max. input current12 A12 A

Output (AC)  
Nominal AC power2300 W2750 W
Max. AC power2500 W3000 W
Max. output current12.5 A15 A
Nominal AC voltage / AC operating range220 V – 240 V / 180 V – 260 V220 V – 240 V / 180 V – 260 V
AC grid frequency (self-adjusting) / range50 Hz / 60 Hz / ±4.5 Hz 50 Hz / 60 Hz / ±4.5 Hz
Phase shift (cos φ)11
AC connection single-phasesingle-phase

Data Sheet

                                                                                                                                                                                              Back to top


 

WINDY BOY 3300 / 3800  

With a maximum efficiency of 95.6 %, the Windy Boy 3300 and 3800 rank among the most profitable inverters for small wind energy plants. The weather-proof casing and the wide temperature range enable installation at almost any location, and thanks to the OptiCool cooling system, the equipment works at outdoor temperatures of up to 45 °C with maximum output. The programmable MPP characteristic curve enables an optimal adjustment to the characteristic curve of the turbine and thus increases the yield. And should a problem arise: the worldwide SMA Service and comprehensive warranty program provide maximum security.

  • Up to 95.6 % efficiency
  • OptiCool: continuous operation even at high temperatures
  • Freely configurable MPP characteristic curve
  • Free choice of installation site
  • Free choice of turbines thanks to programmable characteristic curve
  • Certified for the most important countries of installation (SMA Grid Guard)
  • Galvanic isolation
  • Compatible with the Windy Boy Protection Box 500
  • Protection of the turbine through smooth start
  • Worldwide SMA Service including Serviceline
  • Comprehensive SMA warranty program

Input (DC)WB3300WB3800
Max. DC power3820 W4040 W
Recommended generator power at 2500 full-load hours per year3100 W3600 W
Recommended generator power at 5000 full-load hours per year2800 W3300 W
Max. DC voltage500 V500 V
Min. open circuit voltage for activating "turbine mode"200 V200 V
Operating range "turbine mode"200 V – 500 V200 V – 500 V
Max. input current20 A20 A
Output (AC)  
Nominal AC power3300 W3800 W
Max. AC power3600 W3800 W
Max. output current18 A18 A
Nominal AC voltage / AC operating range220 V – 240 V / 180 V – 260 V220 V – 240 V / 180 V – 260 V
AC grid frequency (self-adjusting) / range50 Hz / 60 Hz / ± 4.5 Hz50 Hz / 60 Hz / ± 4.5 Hz
Phase shift (cos φ)11
AC connectionsingle-phasesingle-phase
Data Sheet

                                                                                                                                                                                             Back to top
  

 WINDY BOY 5000A / 6000A

The Windy Boy 5000A and 6000A not only feature a maximum efficiency of 96.1% but are also suited for the development of three-phase grid-feeding wind energy plants. The integrated SMA Power Balancer prevents undue load unbalance, and, in addition, the plant is able to feed-in even if individual phases fail. The weather-proof casing and the wide temperature range allow for installation at almost any location, and thanks to the OptiCool cooling system, the equipment works at outdoor temperatures of up to 45°C with maximum output. And in case of a problem: The worldwide SMA Service and the comprehensive warranty program provide maximum security.

  • Up to 96.1% efficiency
  • Can be combined to form three-phase units with up to 18 kW output
  • Integrated SMA Power Balancer
  • OptiCool: continuous operation even at high temperatures
  • Choice of installation site
  • Free choice of turbines thanks to programmable characteristic curve
  • Certified for the most important countries of installation (SMA Grid Guard)         
  • Galvanic isolation
  • Compatible with the Windy Boy Protection Box 600
  • Worldwide SMA Service including Serviceline
  • Comprehensive SMA warranty program      

                                                   

Input (DC)WB5000AWB6000A
Max. DC power5750 W6300 W
Recommended generator power at 2500 full-load hours per year4600 W5500 W
Recommended generator power at 5000 full-load hours per year4200 W5100 W
Max. DC voltage600 V600 V
Operating range "turbine mode"246 V – 600 V246 V – 600 V
Min. open circuit voltage for activating "turbine mode"250 V250 V
Max. input current26 A26 A
Output (AC)  
Nominal AC power5000 W6000 W
Max. AC power5500 W6000 W
Max. output current26 A26 A
Nominal AC voltage / AC operating range220 V – 240 V / 180 V – 260 V220 V – 240 V / 180 V – 260 V
AC grid frequency (self-adjusting) / range50 Hz / 60 Hz / ± 4.5 Hz50 Hz / 60 Hz / ± 4.5 Hz
Phase shift (cos φ)11
AC connection single-phasesingle-phase
                                                                                                                                                                                              Back to top

Windy Boy Protection Box

Rectifier and overvoltage protection – the Windy Boy Protection Box from SMA is multitalented: it protects the inverter from excessive generator voltage, while at the same time, it diverts excess power into a load resistor. In addition, the Windy Boy Protection Box features a 3-phase rectifier. It is delivered as a turnkey unit and can be used with nearly all types of generators from various manufacturers and with different power classes. This makes the Windy Boy Protection Box the optimal solution for wind power plants, but it also provides the perfect link between permanent magnet generators and the inverter.

  • Highly dynamic overvoltage protection
  • Optimal start-up performance of the wind turbine
  • High efficiency of the integrated rectifier
  • Feed-in even at excessive generator voltage
  • Easy installation
  • 3-phase generator connection
  • Available in three voltage classes: 400, 500 and 600 V

GeneralWindy Boy Protection Box 400Windy Boy Protection Box 500Windy Boy Protection Box 600
Suitable forWB 1100, WB 1700WB 3300, WB 3800WB 2500, WB 2800i, WB 3000, WB 5000A, WB 6000A
Rectifierintegratedintegratedintegrated
Size (W x H x D) in mm280 x 220 x 130280 x 220 x 130280 x 220 x 130
Weight5 kg5 kg5 kg
Generator connection   
Quantity1 x 3-phase1 x 3-phase1 x 3-phase
AC voltage3 x 0 to 500 V3 x 0 to 500 V3 x 0 to 500 V
AC current3 x 0 to 11.5 A3 x 0 to 11.5 A3 x 0 to 11.5 A
Generator frequency0 to 400 Hz0 to 400 Hz0 to 400 Hz
Nominal power1 to 2 kW3 to 4 kW2 to 6 kW
                                                                                                                                                                                              Back to top

Complete Windy Boy Data Sheet

If you cannot find the product you are looking for please contact us on 0845 3022 873 to discuss your specific requirements. Alternatively you can email your request for product information and prices to info@solenttech.co.uk

                                                   We look forward to hearing from you


 